四、设计依据
1. 采暖通风与空气调节设计规范(GBJ 19-87-2001)
2. 民用建筑暖通空调设计技术措施(第二版)
3.《暖通空调制图标准》(GB/T 50114-2001)
4. 民用建筑防排烟技术规范(DGJ 08-88-2000)
五、参数                                
                          上海室外气象参数
季节            干球温度           湿球温度        相对湿度
夏季            34.6℃              28.2℃           69%
冬季            -1.2℃               ―              74%
                            上海室内参数
夏季温度        26℃               相对湿度          50%
冬季温度        18℃               相对湿度          18%
General description of the design
A, project overview
    Shanghai Port International Hotel D district (District Office), located in Shanghai City, a total construction area of 5528.76m2, a total of four. Building height of 17.1 meters, one to three layers for the office, including the manager's office, office, financial room, large conference room, auditorium, room etc.. Floors are 4.2 meters; the fourth layer is the engine room equipment rooms, floors to 4.5 meters, with tanks, cooling towers, chillers, boilers, etc..
Two, system design
1. load calculation
1) The building of four floors, including top-level room. 1-3 layer of 4.2 meters high; the 4 layer of 4.5 meters high. Outside the window height is 1.8 meters, air-conditioning the use of an area of 2496.57㎡.
2) The need for air conditioning area: general manager's office, office, office, lobby manager, financial room, large conference room, auditorium.
3) Fresh air volume according to personnel density, 30m ³ /h.
4) Office personnel density 0.18 / ㎡.
5) The room lighting power: office, general manager office, financial room, large conference room 18W/ square meters. Office, room 11W/ ㎡.
6) Room equipment power: office, general manager office, financial room, large conference room 13W/ square meters. 20W/ square meters of office. The 5W/㎡.
7) Maintain the value structure of the heat transfer coefficient:
①The external use of concrete 26-175 type external wall, heat transfer coefficient is 0.97K (w/ ㎡.℃).
②The window with double-layer alloy hollow glass window, heat transfer coefficient is 3.31K (w/ ㎡.℃).
③The outer door double-layer metal door, filled with 15 ~ 18 thick mineral wool board, the heat transfer coefficient of 3.15K (w/ m.℃).
④The inner door metal door, filled with 15 ~ 18 thick mineral wool board, the heat transfer coefficient of 3.15K (w/ ㎡.℃).
⑤The use of prefabricated 01-1-35-1 roof, heat transfer coefficient is 1.26K (w/ ㎡.℃).
上一篇:十二层公司办公楼中央空调系统设计+CAD图纸
下一篇:国际酒店暖通空调系统设计+CAD图纸+计算书

南京某酒店暖通空空调工程设计

高层建筑中央空调送风系...

秦皇岛北戴河某假日酒店建筑及结构设计

镇江某酒店暖通空调系统设计+CAD图纸

宁波市锦江酒店中央空调系统设计+CAD图纸

台州香格里拉酒店暖通空调工程设计

成都某酒店空调系统设计+CAD图纸

拉力采集上位机软件开发任务书

多元化刑事简易程序构建探讨【9365字】

中国古代秘书擅权的发展和恶变

浅谈新形势下妇产科护理...

辩护律师的作证义务和保...

国内外无刷直流电动机研究现状

高校网球场馆运营管理初探【1805字】

《醉青春》导演作品阐述

谷度酒庄消费者回访调查问卷表

浅谈传统人文精神茬大學...