The installation of HVAC equipment is a huge project, which is very complicated and different uses.. For example a complete HVAC design to covers of all equipment and pipes in the air terminal equipment, the wind sending pipe, exhaust pipe, chilled water, electrical bridge, condensation water pipe and a spray pipe, fire tube design. If some functions and sizes of pipeline layout, planning unreasonable, there will appear pipeline elevation, positioning cross serious phenomenon, to engineering construction and management to bring great difficulties. Usually in the drawings, unclear meaning hastily construction will cause the first installation of pipeline construction is easy to install, installation construction, so that some pipeline is forced to install in unreasonable position or elevation, seriously affect the engineering quality and progress, in view of the above problems should be integrated design of pipelines.
The air conditioning system design of Furong building located in Shanghai, the building height of 17.7m, building area of 1285 square meters of air conditioning. Building ground floor, ground floor 5, underground one for the equipment, the ground floor of the one or two floors for the hall, the duty room and dormitory, three to five for the dormitory.
The design standards in strict accordance with the relevant standards promulgated by the state as well as the details of the task given in the book, which indoor design of the main parameters as follows:
Hall: summer indoor temperature is 25 degrees Celsius, relative humidity is 60%, the winter indoor temperature is 18 degrees Celsius, relative humidity is 40%, the amount of fresh air is 30m and noise standards around 35-40NC.
Dormitory: summer indoor temperature is 25 degrees Celsius, relative humidity is 60%, the winter indoor temperature is 18 degrees Celsius, relative humidity is 40%, the amount of fresh air is 30m and noise standards around 35-40NC.
Duty room: summer indoor temperature of 25 degrees Celsius, relative humidity is 60%, the winter indoor temperature is 18 degrees Celsius, relative humidity is 40%, the amount of fresh air is 30m and noise standards around 35-40NC.
The main principle of this design is energy saving economy.. Shanghai lotus building is mainly used for dormitory, so air conditioning design is no need to be too accurate, designed to comfort and easy economy can.
Shanghai lotus building is a comprehensive building, it contains the hall, the duty room and dormitory. According to the meteorological conditions of Shanghai, and the air conditioning design, the basic scheme of the design was set up.. Uses the design of fan coil unit plus fresh air semi central air conditioning system, the centralized system applicable room area is big but the wind pipe is not easy to layout; multi room storey low, heat and moisture load is not consistent or parameters require different; request the indoor air not collusion, adjustable air volume. Of a semi centralized system flexibility, good energy-saving effect, can adjust itself according to the load on the indoor coil in winter and summer dual-purpose. System cooling load by the screw type water chiller supply, heating supply by regional boiler room room does not need also for cold and heat, so the selection of closed two pipe system, cold water and the hot water in common use a pipeline, has the advantages of simple system, the need to overcome the hydrostatic pressure, water pump pressure and power were low, the initial investment is low. The arrangement of dry pipe adopts horizontal type pipe, the choice of different programs, the first grade pump and the pump variable flow system.
目录
1  绪论    1
1.1. 暖通空调设计概述    1
2  原始资料    2
2.1. 建筑概况    2
3  设计规范及依据    3
3.1. 设计范围    3
3.2. 设计依据    3
4  设计参数    4
上一篇:某小区锅炉房设计+CAD图纸
下一篇:实验学校教学楼框架建筑与结构设计+CAD图纸+计算书

上海华漕镇社区图书馆建筑与结构设计

某会议综合楼的消防设计

海南省三亚市某综合购物广场的空调系统设计

南京某酒店暖通空空调工程设计

南京市某医院门诊楼空调系统设计

四层某校综合楼消防设计

上海港张华浜港区9#集装箱...

辩护律师的作证义务和保...

《醉青春》导演作品阐述

中国古代秘书擅权的发展和恶变

高校网球场馆运营管理初探【1805字】

国内外无刷直流电动机研究现状

多元化刑事简易程序构建探讨【9365字】

谷度酒庄消费者回访调查问卷表

浅谈传统人文精神茬大學...

浅谈新形势下妇产科护理...

拉力采集上位机软件开发任务书