2008    4    30    120    3    0.0111    0.12×0.1    2.778
续表 4.2  各楼新风管截面尺寸
二层    2009    8    30    240    3    0.0222    0.2×0.12    2.778
    2010    8    30    240    3    0.0222    0.2×0.12    2.778
    2011    8    30    240    3    0.0222    0.2×0.12    2.778
    2012    5    30    150    3    0.0139    0.12×0.12    2.894
    2013    5    30    150    3    0.0139    0.12×0.12    2.894
十层    10001    4    30    120    3    0.0111    0.12×0.1    2.778
    10002    3    30    90    3    0.0083    0.1×0.1    2.500
    10003    3    30    90    3    0.0083    0.1×0.1    2.500
    10004    6    30    180    3    0.0167    0.16×0.12    2.604
    10005    6    30    180    3    0.0167    0.16×0.12    2.604
    10006    6    30    180    3    0.0167    0.16×0.12    2.604
    10007    4    30    120    3    0.0111    0.12×0.1    2.778
    10008    4    30    120    3    0.0111    0.12×0.1    2.778
    10009    8    30    240    3    0.0222    0.2×0.12    2.778
    10010    8    30    240    3    0.0222    0.2×0.12    2.778
    10011    20    30    600    3    0.0556    0.25×0.25    2.667
注:二至九层房间新风管截面尺寸一样

5    空调水系统设计与计算
通风管道的水力计算是在系统和设备布置、风管材料、各送排风点的位置和风量均已确定的基础上进行的。其主要目的是,确定各管段的管径(或断面尺寸)和阻力,保证系统内达到要求的风量分配。最后确定风机的型号和动力消耗。在有的情况下,风机的风量、风压已经确定,要由此去确定风管的管径。
5.1    水系统的比较、选择
空调水系统包括冷水系统和冷却水系统两个部分,它们有不同类型可供选择。