=900kW, =0.80,tan =0.70
  =  =900 0.80=720kW
 = tan= 720 0.70=504kvar
   传送机:
 =42kW, =0.80,tan =0.70
  =  =42 0.80=33.6kW
 = tan =33.6 0.70=23.52kvar
表2-1  仿炼车间负荷统计表
序号    车间设备名称    安装容量/kW    
tan
 /kW
 /kvar

1    纺丝机    180    0.80    0.78    144    112.32
2    绞筒机    62    0.75    0.75    46.5    34.875
3    烘干机    78    0.75    1.02    58.5    59.67
4    脱水机    20    0.60    0.80    12    9.6
5    通风机    200    0.70    0.75    140    105
6    淋洗机    14    0.75    0.78    10.5    8.19
7    变频机    900    0.80    0.70    720    504
8    传送机    42    0.80    0.70    33.6    23.52
小计        1496            1165.1    857.175
(2)纺炼车间总计算负荷统计
取同时系数 =0.9, =0.95
 =  =0.9 1165.1=1048.59kW                                   (2-3)
 =  =0.95 857.175=814.33 kvar                             (2-4)
 = = =1328kVA                        (2-5)
二、原液车间照明
 =1012kW, =0.75,tan =0.70
  =  =1012 0.75=759kW
 = tan =759 0.70=531.3kvar
 = = =926.4kVA
三、酸站照明
 =304kW, =0.65,tan =0.70
  =  =304 0.65=197.6kW
 = tan =197.6 0.70=138.32kvar
 = = =241.2kVA
四、锅炉房照明
 =280kW, =0.75,tan =0.75
  =  =280 0.75=210kW
 = tan =210 0.75=157.5kvar
 = = =262.5kVA
五、排毒车间照明
 =186kW, =0.70,tan =0.60
  =  =186 0.70=130.2kW
 = tan =130.2 0.60=78.12kvar
 = = =151.8kVA
吹冰、其他车间照明
 =380kW, =0.70,tan =0.75
  =  =380 0.70=266kW
 = tan =266 0.75=199.5kvar
 = = =332.5kVA

表1-2  各车间计算负荷统计列表
序号        车间名称    安装容量/kW     /kW
 /kvar
 /kVA

1        纺炼车间    1496    1048.59    814.33    1328
2        原液车间    1012    759    531.3    926.4
3        酸站    304    197.6    138.32    241.2
上一篇:Saber高频环节矩阵式变换器的分析与设计
下一篇:Matlab的分数阶控制系统仿真研究

10kv变电所的设计

单级升降压型PWM整流电路的研究

多媒体监控系统茬变电所的應用【1038字】

变电所的防雷措施【614字】

冶金企业110kv总降压变电所的设计

220kV变电所电气部分设计

110KV变电所设计

《水浒传》中血腥暴力研...

遥感土地用变化监测国内外研究现状

PCI+PID算法直流力矩电机速...

浅析施工企业保理融资成...

提高小學语文課堂朗读教...

高效课堂教师问卷调查表

从企业eHR建设谈管理信息...

大规模MIMO系统的发展研究现状

MNL模型历史城区居民活动...

小型通用机器人控制系统设计任务书