ASHRAE Standard 55 also addresses the effect of these variables
on comfort. In establishing the supply air temperature, the initial
cost of lower airflow and low air temperature (smaller fan and duct
systems) must be calculated against the potential problems of dis-
tribution, condensation, air movement, and the presence of in-
creased odors and gaseous or particulate contaminants. Terminal
devices that use low-temperature air can reduce the air distribution
cost. These devices mix room and primary air to maintain reason-
able air movement in the occupied space. Because the amount of
outside air needed is the same for any system, the percentage in low-
temperature systems is high, requiring special care in design to
avoid freezing of preheat or cooling coils. Also, the low-tempera-
ture air supply reduces humidity in the space. Lower humidity dur-
ing cooling cycles costs more in energy because the equipment runs
longer. Also, if the humidity is too low, it may cause respiratory
problems.
 
Other Considerations
All-air systems operate by maintaining a temperature differential
between the supply air and the space. Any load that affects this dif-
ferential and the associated airflow must be considered. Among
these loads are the following: 
• All fans (supply, return, and supplemental) add heat. The effect of
these gains can be considerable, particularly in process work. If
 
Energy
the fan motor is in the airstream, the inefficiencies in the motor
must also be counted as heat gain to the air. If the fan is placed
after the cooling coil (draw-through,) the total pressure (static
plus velocity pressure) must be calculated. If the fan is placed
before the coil (blow-through), only the velocity pressure needs
to be considered, and the amount of supply air can be reduced.
The heat gain in medium-pressure systems is about 1 K per kilo-
pascal static pressure.
• The supply duct may gain or lose heat from the surroundings.
Most energy codes require that the supply duct be insulated,
which is usually good practice regardless of code requirements.
• Attempting to control humidity in a space can affect the quantity
of air and become the controlling factor in the selection of supply
airflow rate. VAV systems provide only limited humidity control,
so if humidity is critical, extra care must be taken in design.
First, Operating, and Maintenance Costs
As with all systems, the initial cost, or first cost, of an air-han-
dling system varies widely depending on location, condition of the
local economy, and preference of the contractor—even for identical
systems. For example, a dual-duct system is more expensive
because it requires essentially twice the amount of material for ducts
as that of a comparable single-duct system. Systems requiring
extensive use of terminal units are also comparatively expensive.
The operating cost depends on the system selected, the skill of the
designer in selecting and correctly sizing components, the effi-
ciency of the duct design, and the effect of the building design and
type on the operation. All-air systems have the greatest potential to
minimize operating cost.
Because an all-air system separates the air-handling equipment
from the occupied space, maintenance on major components in a
central location is more economical. Also, central air-handling
equipment requires less maintenance than other comparable equip-
ment. The many terminal units used in an all-air system do, how-
ever, require periodic maintenance. Because these units (including
reheat coils) are usually installed throughout a facility, maintenance
costs for these devices must be considered.
上一篇:水力碎浆机英文文献和参考文献
下一篇:回收塑料材料注射成型英文文献和中文翻译

AngularJS技术介绍英文文献和中文翻译

开关电源水冷却系统英文文献和中文翻译

减数分裂和基因重组英文文献和中文翻译

太阳能最大功率点追踪和...

移动码头的泊位分配问题英文文献和中文翻译

虚拟船舶装配集成建模方...

中学生科学探究中对等论...

从政策角度谈黑龙江對俄...

STC89C52单片机NRF24L01的无线病房呼叫系统设计

基于Joomla平台的计算机学院网站设计与开发

浅论职工思想政治工作茬...

AES算法GPU协处理下分组加...

浅谈高校行政管理人员的...

酵母菌发酵生产天然香料...

上海居民的社会参与研究

提高教育质量,构建大學生...

压疮高危人群的标准化中...