simply specifying look-up tables. The former modeling approach is
usually used for secondary system component descriptions, while for
primary system components, due to their complexity, the latter
approaches are more often used, but exceptions exist [29].
3.2. Modeling approaches for HVAC control
HVAC controllers can be pided into two categories as follows.
Local controllers are low-level controllers that allow HVAC systems
to operate properly and to provide adequate services. Local controllers
can be further subpided into two groups [30]:
• Sequencing controllers define the order and conditions associated
with switching equipment ON and OFF. Typical sequencing controllers
in HVAC systems are chiller sequencing controller, cooling tower
sequencing controller, pump sequencing controller, fan sequencing
controller, etc.
• Process controllers adjust the control variables to meet the
required set point in spite of disturbances and considering the system
dynamic characteristics. The typical process controllers used in the
HVAC field are P, PI, PID, ON/OFF, step controller, etc.
Supervisory controllers are high level controllers that allow
complete consideration of the system level characteristics and
interactions among all components and their associated variables.
For example, a supervisory controller sets operation modes and sets
points for local controllers.
From a modeling point of view, controllers are represented by
equations that must be satisfied in every simulation step. The
controllers direct the interaction between building and system as
well as interactions between components within the system.
In reality, the closed-loop local-process control includes a sensor
that samples a real-world (measurable) variable. The controller, based
on the set point value and measured value, and according to the
controller-specific control algorithm, calculates the control signal that
feeds the real-world actuator. However, in the simulation tool the
user can address variables that cannot be sensed or actuated in reality,
as well as apply control algorithms that do not exist in reality. For
example, a modeler can directly actuate the heat flux in a model
where in reality this could only be done indirectly by changing a
valve/damper position.
Furthermore, due to the accessibility ofmany variables not directly
known in the real world, such as the zone cooling/heating load, in
simulation the concept of “ideal” (local process) control becomes
feasible. An “ideal” local-process controller means that the actuated
variable will be adjusted to satisfy the set point requirements for the
controlled variable, without specifying the explicit control algorithm
and by numerically inverting the (forward) simulation models (from
the required output calculate the input needed to satisfy this).
Possibilities to simulate different (advanced) controllers in state-
of-the-art BPS tools are limited. Some tools offer pre-defined control
strategies (system-based simulation tools), some offer flexibility in
specifying only supervisory controllers (EnergyPlus) and some even
in specifying local controllers (TRNSYS, ESP-r). The domain-indepen-
dent environments, such as MATLAB and Dymola, are efficient tools
for designing and testing of controllers in a simulation setting, but lack
the models of all other physical phenomena in buildings.
3.3. Modeling approaches for HVAC systems
Hensen [31] defines four categories of HVAC system representa-
tion in BPS tools, ranging from purely conceptual towards more
explicit, as follows.
Pure conceptual system modeling approach represents the case
where only room processes are considered, while all other processes
上一篇:五轴端铣英文文献和中文翻译
下一篇:数字式EL定位器英文文献和中文翻译

建筑自动化英文文献和中文翻译

新能源空调系统设计英文文献和中文翻译

机械设计制造及其自动化英文文献和中文翻译

超市空调系统英文文献和中文翻译

船舶自动化系统英文文献和中文翻译

PLC自动化制造系统英文文献和中文翻译

南京某软件园研发楼空调系统设计

浅论职工思想政治工作茬...

基于Joomla平台的计算机学院网站设计与开发

压疮高危人群的标准化中...

浅谈高校行政管理人员的...

STC89C52单片机NRF24L01的无线病房呼叫系统设计

从政策角度谈黑龙江對俄...

提高教育质量,构建大學生...

酵母菌发酵生产天然香料...

上海居民的社会参与研究

AES算法GPU协处理下分组加...