Walk-in Spray Paint Booths。  The ventilation system for a walk-in booth is mainly to prevent fire and explosion。 A well-designed ventilation system will also

reduce paint overspray, help control workers’ exposure, and protect the paint finish。 Workers must use appropriate respiratory protection irrespective of the airflow rate。 On 9 February 2000, OSHA issued an interpretation of 29 CFR 1910。94 and 1910。107, Spray Finishing Using Flammable and Combustible Materials for determining the airflow rate required for a walk-in paint booth。 In accordance with OSHA’s interpretation letter, following NFPA 33 will provide protection from fire and explosion。  The guidance listed in Subpart Z of 29 CFR 1910。94 provides protection for workers。 See Appendix B for OSHA’s interpretation。

a。 Use the Painting Operations section in the ACGIH IV manual to determine the design volumetric airflow rate。 Ensure that this design volumetric airflow rate will keep the concentration of vapors and mists in the exhaust stream of the ventilation system below the 25 percent of the LEL。 See 1910。94(c)(6)(ii) for an example of airflow rate requirement calculations。

b。 Do not re-circulate exhaust air while painting。

9-3。1。1 Exhaust Configurations。  The two main ventilation system configurations are downdraft and crossdraft。 In a downdraft booth, air enters through filters in the ceiling of the booth and leaves through filters that cover trenches under a metal grate floor。 In a crossdraft booth, air enters through filters in the front of the booth and leaves through filters in the back of the booth。 Both configurations are commercially available。

9-3。1。1。1 Downdraft Paint Spray Booths。 Downdraft booth configuration provides a cleaner paint job than the crossdraft booth configuration and controls exposures to workers better than crossdraft booth configuration。 The downdraft configuration should be the primary choice in designing or selecting of paint spray booths。 Figure 9-1 is an example of a downdraft configuration。

9-3。1。1。2 Crossdraft Paint Spray Booths。  The crossdraft paint spray booth usually requires less total volumetric airflow rate than the downdraft spray paint booth because the vertical cross-sectional area of the booth is often smaller than the booth footprint area。 Figures 9-2 and 9-3 are examples of drive-through crossdraft paint spray booth configurations。

Figure 9-1。  Walk-in downdraft paint booth。

NOTES:

1。 Size each plenum take-off for no more than 2。44 m (8 ft) of plenum width (W)。

2。 Perforated plate with 9。53-mm (3/8-in) holes。 Size open area for an airflow velocity of 5。08 m/s (1,000 fpm) through holes。

3。 Size exhaust plenum for a maximum plenum velocity of 5。08 m/s (1,000 fpm)。 Size replacement air plenum for a maximum plenum velocity of 2。54 m/s (500 fpm)。

4。 Use manufacturer’s recommendations for sizing perforated ductwork。

5。 Removable filters and floor grating。

Figure 9-2。 Drive-through cross draft paint booth with mechanical replacement air。

NOTES:

1。 Size each plenum take-off for no more than 2。44 m (8 ft) of plenum width。 Size the exhaust plenum for a maximum plenum velocity of 5。08 m/s (1,000 fpm)。 Size replacement air plenum for a maximum plenum velocity of 2。54 m/s (500 fpm)。

2。

上一篇:基于网络的注塑模具智能设计英文文献和中文翻译
下一篇:三维有限元分析英文文献和中文翻译

张家港某舾装码头工程设计+CAD图纸

阻尼减震平台的设计英文文献和中文翻译

兰州某大酒店空调设计+CAD图纸

新能源空调系统设计英文文献和中文翻译

机械设计制造及其自动化英文文献和中文翻译

FPGA的全景拼接相机的优化...

海水淡化的优化设计英文文献和中文翻译

STC89C52单片机NRF24L01的无线病房呼叫系统设计

浅谈高校行政管理人员的...

上海居民的社会参与研究

基于Joomla平台的计算机学院网站设计与开发

AES算法GPU协处理下分组加...

从政策角度谈黑龙江對俄...

浅论职工思想政治工作茬...

压疮高危人群的标准化中...

提高教育质量,构建大學生...

酵母菌发酵生产天然香料...